Description
Zurn Wilkins 114-975XL 1-1/4″ RPZ Reduced Pressure Backflow Preventer
Product Overview
The Zurn Wilkins 114-975XL 1-1/4″ RPZ Reduced Pressure Principle Assembly is a bronze backflow preventer designed to protect potable water supplies against both backsiphonage and backpressure from contaminated water. Supplied with full-port QT ball valves and female NPT threaded connections, it provides high-hazard cross-connection protection for commercial plumbing, irrigation, mechanical equipment, industrial water systems, and other approved non-potable applications.
The Model 975XL features a compact wye-pattern bronze body that provides direct access to the first and second check assemblies without requiring removal of the relief valve or the complete device from the pipeline. This service-friendly design helps reduce maintenance time, labour requirements, and system downtime.
Cast-bronze construction, stainless steel fasteners and springs, Noryl™ internal polymers, and silicone and Buna-N elastomers provide durable performance in demanding commercial and industrial installations. The 1-1/4″ model offers increased flow capacity while retaining the compact, service-friendly design of the 975XL series.
Key Features & Benefits
- Protects against both backsiphonage and backpressure
- Designed for high-hazard cross-connection protection
- Includes an integrated relief valve
- Supplied with full-port QT ball valves
- 1-1/4″ female NPT threaded inlet and outlet connections
- Compact wye-pattern bronze body reduces installation space
- First and second check assemblies are accessible in-line
- Checks can be serviced without removing the relief valve
- Complete assembly can remain installed during routine internal maintenance
- Cast-bronze main valve body and access covers
- 300 Series stainless steel fasteners and springs
- Noryl™ internal polymer components
- Silicone and Buna-N elastomers
- Maximum working pressure of 175 PSI
- Maximum working water temperature of 180°F
- Hydrostatic test pressure of 350 PSI
- ASSE® 1013 listed reduced pressure assembly
- Compatible air gap, strainer, repair kits, and testing accessories available separately
Why Choose the Zurn Wilkins 975XL?
The Zurn Wilkins 975XL combines durable bronze construction with convenient in-line service access. Its wye-pattern configuration allows technicians to reach the first and second check assemblies without removing the relief valve or taking the complete backflow preventer out of the piping system.
The 114-975XL is well suited to higher-flow commercial, irrigation, mechanical, institutional, and industrial systems requiring reduced pressure principle protection. Its integrated relief valve, threaded connections, high-temperature capability, and established approval profile make it a dependable choice for demanding installations.
The compact footprint also makes the 1-1/4″ model practical for mechanical rooms, utility spaces, and retrofit applications where serviceability and available installation space are important.
Typical Applications
- Commercial plumbing systems
- Irrigation and sprinkler systems
- Boiler and HVAC make-up water connections
- Mechanical equipment connections
- Industrial process-water systems
- Institutional facilities
- Laboratory equipment
- Water treatment equipment
- Other high-hazard non-potable applications
The Model 975XL protects the potable water supply from a connected hazard, but Zurn specifies the assembly for non-potable applications only. Final product selection and installation must comply with local plumbing codes, cross-connection-control requirements, and the authority having jurisdiction.
Engineering Specification
The Reduced Pressure Principle Backflow Preventer shall be ASSE® Listed 1013, rated to 180°F, and supplied with full-port ball valves.
The main valve body and access covers shall be cast bronze conforming to ASTM B584. The seat rings and internal polymer components shall be Noryl™, and the seat-disc elastomers shall be silicone. Fasteners and springs shall be manufactured from 300 Series stainless steel.
The first and second check assemblies shall be accessible for maintenance without removing the relief valve or the complete assembly from the pipeline. Where installed indoors, the installation shall include an air-gap adapter. The assembly shall be intended for non-potable applications and shall be a Zurn Wilkins Model 114-975XL.
Product Specifications
| Specification | Details |
|---|---|
| Manufacturer | Zurn Wilkins |
| Model | 114-975XL |
| Series | 975XL |
| Assembly Type | Reduced Pressure Principle Assembly |
| Common Abbreviation | RP / RPZ |
| Nominal Size | 1-1/4″ / DN32 |
| Shut-Off Valves | Full-Port QT Ball Valves |
| End Connections | Female NPT Threaded |
| Thread Standard | ANSI B1.20.1 |
| Maximum Working Pressure | 175 PSI / 12.1 bar |
| Maximum Working Temperature | 180°F / 82°C |
| Hydrostatic Test Pressure | 350 PSI / 24.1 bar |
| Main Body Material | Cast Bronze, ASTM B584 |
| Access Cover Material | Cast Bronze, ASTM B584 |
| Fasteners | 300 Series Stainless Steel |
| Springs | 300 Series Stainless Steel |
| Elastomers | Silicone and Buna-N |
| Internal Polymers | Noryl™ |
| Relief-Valve Discharge-Port Area | 1.19 sq. in. / 768 mm² |
| Application Classification | Non-Potable Applications Only |
| Order Number | 114-975XL |